Boost mode, Sensor fault, Setting the control to factory defaults – LAARS M4-Ext - Installation Manual User Manual

Page 20: Alert

Advertising
background image

20

• When Shutdown or Tstat is selected, the Day/Night Schedules will be available in the operating menu. See "Shutdown/Tstat/

Setback Mode" on page 19. Terminals 31 and 32 will function as a Shutdown (Turn off boilers when shorted) or as a Tstat (Turn off

boilers when opened). However, a call for DHW will bring the boilers on.

• When Setback is selected, the External Signal option will switch the M4-CNC to Setback mode when terminals 31 and 32 are

shorted. This allows an external device or control to provide the setback signal. No scheduling or boost menu options will be

available with Setback.

BOOST MOdE

(noT AvAiLABLE wiTH EXTERnAL SETBACk inPuT)

30 Minutes, Disabled

Default: 30 Minutes

Button: MENU/<System Startup>/..../Boost Mode

• The morning Boost is designed to return the building to comfortable ambient temperatures

after the cooler Night (Setback) period. The M4-CNC will accomplish this by running

elevated water temperatures (will add Setback setting to calculated water temperature) for

30 minutes before the start of the Day schedule setting. That is, if the normal day set point

at a specific outdoor was 145˚F and the Setback setting was 20˚F, the boost will raise the

system calculated temperature to 165˚F for 30 minutes before the start of the Day Schedule

setting.

• If no Boost is needed, then simply select Disabled from the Boost Menu.

• Boost is only available if Shutdown or Tstat is selected as an option. See "Shutdown/Tstat/

Setback Mode" on page 19.

--- BOOST MODE ---

30 Minutes

Disable

BACK ▲ ▼ SAVE

SENSOR FAULT

All Off, All On

Default: All On

Button: MENU/<System Startup>/..../Sensor Fault

• The Sensor Fault will determine the operating status of all output stages that has their Mode

set to Auto when a sensor reads Short or Open.

• When All-On is selected, the M4-CNC will turn all boilers On to 100% when the System

reads Short or Open and the outdoor temperature is below Outdoor Cutoff. However, when

the Outdoor reads Short or Open, the M4-CNC will try to maintain the Maximum Water

Temperature.

• When All-Off is selected, the M4-CNC will turn all boilers Off when either the System or

the Outdoor sensor reads Short or Open. However, when the Outdoor reads Short or Open,

the M4-CNC will try to maintain the Minimum Water Temperature.

--- SENSOR FAULT ---

All Off

All On

BACK ▲ ▼ SAVE

ALERT

A good practice after performing any Startup menu modification is to

check all operating settings and adjustments to match the new settings.

SETTiNg THE CONTROL TO FACTORY dEFAULTS

To Reset the M4-CNC control to its original factory defaults, power down the control.

Hold down the two right most buttons while powering the control back up until the
Total Clear Started screen appears. The Display will direct you to the Startup

menu to program the control after the defaults are loaded.

TOTAL CLEAR STARTED

Release buttons

and

Please Wait

NOTE: When resetting the control to original factory defaults all control settings will be overwritten and will no longer exist.

ALERT

Do not turn off power to control until all Startup settings have been made. Otherwise, the next

power-up will be set to many Startup factory settings that might not fit your application.

LAARS Heating Systems

HT# 059104-00 B