MICROTEL

CellStat

TM


9


If the user enters the correct code, access will be granted and the user may review or
program the dialer’s configuration using the touch-tone commands described in this
manual. If at any time during remote menu access the user does not enter a command
within 30 seconds, the dialer will speak a disconnect warning and hang up.

If an incorrect or no access code is entered during a timed access code entry time (10
seconds), the dialer will disconnect and initialize the system Call Spacing delay timer. If
the alarm condition(s) were acknowledged, then the snooze timer(s) associated with the
reported alarm condition(s) will be initialized with a value equal to the programmed
system Snooze Delay. If alarm conditions were not acknowledged, calls will continue to
be placed to the next telephone numbers on the list after the system Call Spacing delay
has expired.


How can I Make an Alarm Sound in the Vicinity of the Dialer?


The local summary alarm contacts will be de-energized (opened) whenever a fault
condition exists. This output could be connected to an interposing relay whose contacts
would be used to switch a siren or bell to warn the local area of the alarm condition.