MICROTEL

CellStat

TM


33

A.7 Fault Inputs

Type:

Isolated Dry Contact, Normal Open or Normal
Closed, Non-Latched.

Sensing

frequency:

1

Hz


Sensing current:

Closed circuit sees a 10 mA (nominal),
10 millisecond-duration pulse, once every second.


Sensing voltage:

Open circuit sees 5 Volts (nominal)


Max. Loop Resistance:

10 killiohms


Max. Loop Capacitance:

100,000 picofarads


Isolation:

1500 Volts, transformer and optical isolation.


Fault Integration Delay:

00 – 99 seconds


AC Power Fail Detect:

Internal circuit, configurable enable and alarm delay


Cellular Fault Detection: Alert generated when cellular prepaid balance < $5



A.8 Local Summary Alarm Contacts

Type:

Relay, Type 1A Contacts


Operation:

Normally energized (contacts closed),

De-energized (contacts open) when a Fault
condition is present.


Contact Rating:

10 VA, Resistive Load

Max. Switch Current:

0.5 Amp D.C


Max Switch Voltage:

48 Volts D.C.


Max. Carry Current:

1.25 Amps D.C.


Isolation:

1500 Volts