Microtel Series 1000 User Manual

Page 27

Advertising
background image

MICROTEL Series 1000 Dialer

21

Basic System Information Overview


The following commands configure and report the current values for the overall system
level operations of the Series 1000. These settings include:

Section Current

Setting

Change
Setting

Meaning

Voice System Name

*001 **001~ User defined Voice System Name for the

Dialer

Call Spacing Time

*002 **002MM

Time in minutes the dialer waits after
making an answered outgoing call before
making another one

Ring Count

*003 **003nn Waits nn rings before answering an

incoming call

Access Code

*004 **004nnnn

Code to get access to the Dialer during a
callin or callout

Message Repeat
Count

*005 **005nn Number of times the Dialer will repeat the

alarm messages for a callin or callout

Voice Interaction
Delay

*006 **006n Delay time between entering a command and

the dialer responding to this command

Callback
Acknowledge

*008 **008n Enabling Callback Acknowledge.

n=1 Enables it. n=0 Disables it

Snooze Delay Time
Interval

*074 **074

DDHHMM

The delay after which the Dialer will re-arm
an acknowledged alarm so that alarm will
again generate callouts

System Telephone #

*010 **010p**

The Dialer’s telephone number (Required
for faxes to comply with FCC
Regulations)


A Glossary of Dialer Terminology that defines these parameters with respect to the
Series 1000 operation is provided in the Appendix.