29

z I/O Channel Type


*c2

Report I/O channel c TYPE

**c20n

Program I/O channel c TYPE

**c208Cv Program I/O channel c to Follow Channel C’s Value

Selection of I/O channel type (c = 1 to 8 for I/O channels starting at leftmost slot).

n Setting

Meaning

0

SPARE

No Type Selected

1

Digital Input Normally Open

Contact closure Normally Open

2

Digital Input Normally Closed

Contact closure Normally Closed

3

Digital Output

Digital Output that is user definable to
be Open or Closed

4

Analog Output (00.0 - 99.9%)

Analog Output that is user definable to
be at some setting

5

Analog Input (00.0 - 99.9%)

Current Percentage of an input value

6

Local Alarm Output

Digital Output that Closes when there
is a local alarm

8

Follow Channel Output

Digital Output that Closes depending
on the followed channel’s state

(see below)

Example- Command:

**3201

Response: Channel three type is one normally open digital input.

NOTE: When

using

Digital or Analog Outputs, see the section labeled Site

Control.

**c208CV Program I/O channel c to Follow Channel C’s Value

Value Setting

Meaning

C

Followed Channel (1-9)

The I/O Channel whose channel
status is being followed.

V

Type of Follow Channel (1-5)
0) Digital Output Follow Channel
1) Dout Follow Channel Status
2) Dout Follow Channel Alarm
3) Dout Follow Fill Algorithm
4) Dout Follow Empty Algorithm

The condition that this Output
Channel is following.

Example- Command:

**420832

Response:

Channel four type is eight digital output following channel three
alarm
.

z I/O Alarm Configuration Selection of channel c’s alarm operation. For instance,

latched, call on alarm, etc.