Introduction

151450

1-5

continue to act prudently in protecting the premises and the people in their premises
and should properly insure life and property and buy sufficient amounts of liability
insurance to meet their needs.

Requirements and recommendations for proper use of fire alarm systems in-

cluding smoke detectors and other fire alarm devices:

Early fire detection is best achieved by the installation and maintenance of fire
detection equipment in all rooms and areas of the house or building in accordance
with the requirements and recommendations of the current edition of the National Fire
Protection Association Standard 72, National Fire Alarm Code (NFPA 72), the
manufacturer’s recommendations, State and local codes and the recommendations
contained in Guide for the Proper Use of System Smoke Detectors, which is made
available at no charge to all installing dealers. For specific requirements, check with
the local Authority Having Jurisdiction (ex. Fire Chief) for fire protection systems.

Requirements and Recommendations include:

Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing
construction.

It is recommended that more than one smoke detector shall be installed in a
hallway if it is more than 30 feet long.

It is recommended that there shall never be less then two smoke detectors per
apartment or residence.

It is recommended that smoke detectors be located in any room where an alarm
control is located, or in any room where alarm control connections to an AC
source or phone lines are made. If detectors are not so located, a fire within the
room could prevent the control from reporting a fire.

All fire alarm systems require notification devices, including sirens, bells, horns,
and/or strobes. In residential applications, each automatic alarm initiating device
when activated shall cause the operation of an alarm notification device that shall
be clearly audible in all bedrooms over ambient or background noise levels (at
least 15dB above noise) with all intervening doors closed.

It is recommended that a smoke detector with an integral sounder (smoke alarm)
be located in every bedroom and an additional notification device be located on
each level of a residence.

To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards.
At a minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be
followed. A maintenance agreement should be arranged through the local
manufacturer’s representative. Maintenance should be performed annually by
authorized personnel only.

The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to
make sure all sensors and transmitters are working properly.