Model 5600 Installation and Operation Manual

4-20

151450

4.9.2.2 Constant Power

Use constant power for applications that require a constant auxiliary power source.
Power is always present at Constant circuits.

4.9.2.3 Resettable Power

Resettable power is typically used to power beam detectors, flame detectors and
conventional 4-wire smoke detectors. For circuits selected as Resettable, 24 volt
power is always present at the terminals unless a system reset occurs. If a system
reset occurs, power is disconnected from the terminals for 30 seconds, then re-
applied.