Section 3 before you begin installing, 1 what’s in the box, 2 environmental specifications – SilentKnight 5600 User Manual

Page 21: What’s in the box, Environmental specifications

Advertising
background image

151450

3-1

Section 3
Before You Begin Installing

This section of the manual is intended to help you plan your tasks to facilitate a
smooth installation. Please read this section thoroughly, especially if you are installing
a 5600 panel for the first time.

3.1

What’s in the Box?

The 5600 ships with the following hardware:

A cabinet with all hardware assembled

Two keys for the front door

Installation and Operation manual P/N 151450.

Ten 4.7K ohm end-of-line resistors

A battery cable for batteries wired in series

3.2

Environmental Specifications

It is important to protect the 5600 control panel from water. To prevent water damage,
the following conditions should be AVOIDED when installing the units:

Intended for indoor use in dry locations only

Do not mount directly on exterior walls, especially masonry walls (condensation)

Do not mount directly on exterior walls below grade (condensation)

Protect from plumbing leaks

Protect from splash caused by sprinkler system inspection ports

Do not mount in areas with humidity-generating equipment (such as dryers,
production machinery)

When selecting a location to mount the 5600 control panel, the unit should be
mounted where it will NOT be exposed to temperatures outside the range of 0°C-
49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F)
noncondensing.