Section 8 reporting, 1 receivers compatible with the control panel, 2 reporting formats dialer outputs – SilentKnight 5600 User Manual

Page 87: Receivers compatible with the control panel, Reporting formats dialer outputs, Manufacturer model format

Advertising
background image

151450

8-1

Section 8
Reporting

This section lists receivers that are compatible with this control panel, and the reporting
codes sent by the control panel for SIA and Contact ID formats.

8.1

Receivers Compatible with the Control Panel

Table 8-1 shows receivers compatible with the control panel.

Table 8-1: Receivers Compatible with the Control Panel

8.2

Reporting Formats Dialer Outputs

Manufacturer

Model

Format

Silent Knight

Model 9800

SIA and Contact ID

Model 9000 (SIA formats)

SIA

Ademco

Model MX8000 (Contact ID)

Contact ID

Sur-Gard

SG-MLR2-DG (V. 1.64 or higher)

SIA and Contact ID

Osborne Hoffman

Quickalert

SIA and Contact ID

SIA Reporting Format

Contact ID Reporting Format

Event Description

Event

Family

Event Class

(System, Zone,

or Point)

Module

ID #

(if any)

SIA

Event

Code

Parameter

(if any)

Qualifier

Event

Code

Group

#

Contact

#

System Events

System events are reported when either “Report by Zone” is selected.

AC power restore

Trouble System Event

AR

3

301

00

000

AC power lost

Trouble System Event

AT

1

301

00

000

Short circuit removed from SLC commu-
nication loop

Trouble System Event

ER

33

3

332

00

Exp. ID

Short circuit detected on SLC communi-
cation loop

Trouble System Event

ET

33

1

332

00

Exp. ID

Fire drill has begun

Test

System Event

FI

1

604

00

000

Fire drill ended

Test

System Event

FK

3

604

00

000

Panel date has been changed

Trouble System Event

JD

1

625

00

000

Panel time has been changed

Trouble System Event

JT

1

625

00

000

Local programming begin

Trouble System Event

LB

1

627

00

000

Advertising