4 maximum slc address point count, 5 installer code, 4 jumpstart autoprogramming – SilentKnight 5600 User Manual

Page 67: Maximum slc address point count, Jumpstart autoprogramming, Tomatically (see section 6.4)

Advertising
background image

Programming

151450

6-5

6.3.4

Maximum SLC address point count

The 5600 control panel supports a maximum of 25 SLC points to be used within the
159 point address range. The points can be all inputs, all outputs or any combination
of inputs and output points. When more than 25 SLC devices are added to the control
panel, any excess points will indicate a trouble and not be recognized by the panel.

6.3.5

Installer Code

The installer code is factory programmed as 123456. The installer code is required to
learn and remember which SLC devices are connected to the panel. The installer
code can be changed when a PC is used to modify the default programming options.

6.4

JumpStart AutoProgramming

Once the physical installation of SLC devices is finished, the panel will need to learn
which SLC devices and SBUS annunciators are present.

To run JumpStart:

1. Press and hold the “JumpStart” key,

2. Press the installer code after PIN is displayed.

3. During JumpStart, the panel will briefly light up all LEDs and then display “SLC

Prg” on the 7 segment display.

4. When complete the display will be off and programming is complete.

If changes are required that affect address settings for the SLC devices, device types
or number of SLC devices installed you will need to repeat JumpStart to re-learn
which devices are supposed to be present on the system.

IMPORTANT

There is no limit to how often you can run JumpStart. Each time you run this
process it starts fresh and does not remember previously installed devices that
are no longer present.