2.0 CALIBRATION AND SET UP

The TASC Control Console must be calibrated for the various sensors used and programmed with certain information
before it is ready to be used. The calibration and set up processes are not difficult, however; they must be followed
precisely in order to get maximum accuracy out of the system.

2.1 ENGLISH AND METRIC UNITS

The TASC Control Console is capable of operating in two different units of measure, English and Metric.

2.1.1 UNITS FOR EACH POSITION

(Refer to Appendix D for these units in "Handgun Mode".)

FUNCTION

U.S.

METRIC

Speed

Miles/Hour (MPH)*

Kilometers/Hour (KPH)*

Area

Acres (-Ac)*

Hectares (-Ha)*

Chem. Applied

Ounces-U.S. Gallons (TOTAL/Oz)*

#

Liters (TOTAL/Liters)*

#

Chem. Rate

Ounces/Acre (Oz-Ac)*

@

Liters/Acre (RATE/Liters-Ha)*

@

Appl. Rate

U.S. Gallons/Acre (Flow/RATE

Liters/Hectare (Flow/RATE/

GAL./ -Ac)*

Liters-Ha)*

Total Applied

U.S. Gallons (TOTAL/Flow/Gal.)*

Liters (TOTAL/Flow)*

Width

Inches-Feet (TOTAL/Boom/Ft.)*

Meters (TOTAL/Boom/Meters)*

Distance

Feet-Miles (Dist./Ft.)***

Meters-Kilometers (Dist.)*

Prime

Ounces (Oz)

Liters (Liters)

Test Speed

Miles/Hour (MPH)

Kilometers/Hour (KPH)

* Items in parenthesis are the abbreviations that appear on the screen.
** No units displayed
*** No units displayed after roll over of feet to miles or meters to kilometers

#

TOTAL when channel in Non-Peristaltic

@

-Ac when channel is in Non-Peristaltic

2.1.2 CHANGING UNITS

To change units, set the Mode switch to OPERATE and the Display Selector to SPEED. The current speed units are be
displayed. Holding the INC/DEC switch down for approximately 5 sec.causes the display to alternate between U.S and
Metric modes (MPH and KPH). The mode being displayed when the INC/DEC switch is released will be selected.

2.2 PERISTALTIC AND NON-PERISTALTIC INJECTION PUMP MODES

Settingg Channel 1 - 6 Drive Method (TASC 6300/6600 Only)

The TASC 6300 and 6600 Chemical Applicator channels (1 - 6) can use two different drive methods, depending on the

type of equipment being controlled by the individual channel. "Peristaltic Drive" is used for peristaltic injection pumps.

"Non-Peristaltic Drive" is for future development. You should select the "peristaltic" drive method at this time.

NOTE: PLEASE READ THROUGH THE FOLLOWING SECTIONS
COMPLETELY BEFORE YOU BEGIN CALIBRATION!