P. 52 – Toa SX-2000 Series Installation User Manual

Page 52

Advertising
background image

52

Protective cover

Screw

Inside of the protective cover

DIP switch

2.1.2. Failure reset operation method settings (DIp switch 4 operation)

one of the following 2 modes can be selected with the SX-2000Sm's DIP switch 4 to determine the operation

method of the SX-2000Sm’s front-mounted fAult rESEt key and rear-mounted rES terminals of the Date

input terminals.

one touch mode:

Pressing the key once or shorting the terminals once executes the

failure reset.

Accidental operation prevention mode: Performing special operation executes the failure reset.

Note

for the detailed description of the operation method, see the separate operating Instructions, "Detecting fault."

Step 1. remove the protective cover on the SX-2000Sm's front panel by unscrewing it with a Phillips screwdriver.

Step 2. Perform DIP switch setting.

2-1. When selecting one touch mode

Set DIP switch 4 to off.

2-2. When selecting accidental operation prevention mode

Set DIP switch 4 to oN.

Step 3. replace the protective cover.

ON

1 2 3 4 5 6 7 8

ON

1 2 3 4 5 6 7 8

Note: DIP switch 4 is set to the off position

by default.

Advertising