professional must be consulted when heaters are installed where fire sprinklers are present to

ensure that heaters and the fire sprinkler system are properly integrated. Specific guidelines can be

found in NFPA 13 regarding design and specifications for Fire Sprinkler Systems near heaters.

5. VENTILATON

a) It is required that areas above the heater be properly vented to allow for necessary combustion

air and removal of combustion gases.

b) DO NOT obstruct the flow of combustion and ventilation air to this heater. If using a propane

tank, keep the ventilation openings free and clear from debris.

c) Heater must be in a location that allows uniform air pressure around the entire heater.

d) Heaters shall be provided with natural or mechanical means to supply and exhaust at least 4

CFM per 1,000 BTU per hour of heater input. This equates to 150 CFM. Exhaust opening for

removing the flue products shall be above the level of the heaters.

e) Heater ventilation must comply with state and local codes.

6. DESIRED HEATING AREA COVERED

Model

Mounting

Height

Cold-

Breezy

Mild

Well

Protected

Heater

Length

Volts

TEGH48

8ft. – 9ft.

6 ft. x 6 ft

8 ft. x 8 ft.

10 ft. x 10 ft.

48 in.

6 VDC