d) Installation of a drip leg in the gas supply line going to each heater is required to minimize the

possibility of any loose scale or dirt within the gas supply line from entering the heater’s

control system.

e) When checking for gas leaks, do not use an open flame. Use the Leak Test procedures using

liquid soap and water solution

f) For gas supply line pressures in excess of ½ psig, consult the factory or your local

representative.

g) Installation of 1/8” N.P.T. plugged tapping accessible for test gage connections is required

upstream of the gas supply connections to the heater.

3. All gas connections should be made by a qualified technician in accordance with all requirements

of the authority having jurisdiction. The technician must be knowledgeable, specifically trained

and experienced in the installation of this type of gas equipment and related gas system

components and with all precautions required regarding this type of equipment. Some states or

provinces require installation and service personnel to be licensed. If your state or province is such,

be sure your contractor bears the appropriate license. If a person does not meet all requirements

and is not qualified for this installation he/she shall not attempt to repair, replace, install nor do any

other type of work or service to this equipment.

If you do not fully understand these instructions, contact your Twin Eagles representative or the

factory prior to performing installation or servicing.