DIAGNOSTIC TABLE

GENERATOR

SYMPTOM
POSSIBLE CAUSE

CORRECTION

LOW VOLTAGE (UNDER 220 VOLTS LOADED)

Engine Speed too Slow

Check the no-load engine speed with a frequency meter and adjust

the governor to 61.5 Hertz at no-load. Troubleshoot engine and deter-

mine why it will not hold the

proper speed.

Generator Overloaded

Measure load being run and compare with nameplate rating. The

load

on each leg should be as evenly balanced as possible and should not

exceed the rated current on

any leg.

LOW VOLTAGE (UNDER 230 VOLTS NO LOAD)

Engine Speed too Slow

Check the no-load engine speed with a frequency meter and adjust the

governor to 61.5 Hertz at no-load.

Generator Overloaded

Measure load being run and compare with nameplate rating. The

load

on each leg should be as evenly balanced as possible and should not

exceed the rated current on

any leg.

Defective Main Rotor

Measure rotor resistance (Rotating Fields). Check for grounds. Replace

if defective.

Defective Capacitor

Test and replace if defective.

LOW VOLTAGE (3 TO 40 VOLTS)

Loose or Shorted Wires in

Check all wiring and repair as needed.

Control Cabinet

Defective Diode

Follow test procedure and replace if defective.

(Rotating Excitation)

Defective Excitor Winding

Measure the resistance of the two leads connected to the capacitor,

Repair or replace as required. Check for grounds.

Defective Capacitor

Test for opens and shorts. Replace if defective.

(Excitor)

Defective Main Rotor

Measure rotor resistance (Rotating Field). Check for grounds. Replace

if defective.