LOW VOLTAGE (0 VOLTS)

Loss of Residual Magnetism

Flash the exciter stator with a small 9 volt battery. Consult factory for

procedure.

Defective Main Stator

Measure stator resistance (G1 TO N & G3 TO N ).

Check for ground

shorts. Replace if defective.

Short in AC Wiring.

Turn off all circuit breakers for the lights and disconnect all external

loads. Check all the AC wiring in the control cabinet for shorts. Repair

or replace as required.

FLUCTUATING VOLTAGE

Erratic Engine Speed

Refer to the Engine manufacturer’s maintenance manual.

Loose Terminal or Load

Check all AC wiring connections.

HIGH VOLTAGE

Engine Speed too High

Check engine speed, reset to 61.5 HZ no-load.

GENERATOR OVERHEATING

Air Vents Obstructed

Clear obstruction.

High Intake Air

Improve ventilation. Allow at least two feet clearance around generator.

Temperature

ENGINE OVERHEATING

Engine Exhaust Leaking

Repair exhaust system.

into Housing

Generator Overloaded

Measure load being run and compare with nameplate rating. The

load

or

Unbalanced

on each leg should be as evenly balanced as possible and should not

exceed the rated current on any leg.

Shorted Turns in Either the

Measure rotor and stator resistance for shorted turns.

Rotor or Stator

Replace if defective.

GENERATOR NOISY AND/OR VIBRATES

Loose Sheet Metal

Check nuts, bolts and doors for tightness.

Rotor Rubbing

Repair or replace defective part.

Bearing Defective

Replace bearing.

Rotor Unbalanced

Rotors are factory spin balanced on special computer controlled ma-

chines before assembly. Small washers or bars are used as balancing

weights. Check inside the

generator for loose or missing parts. If any

`

balance weights have broken loose, do not run the unit. Consult

your

Winco dealer or the factory.