PAGE 14

Lamp Switches/ Circuit Breaker

No Generator Output

Troubleshoot generator.

Circuit Breaker Trips

Troubleshoot and replace if defective.

Defective Transformer or

Troubleshoot and replace if defective.

Capacitor (Ballast)

Short Circuit in

Trace and repair as required.

Tower Wiring

Defective Breaker

Troubleshoot and replace if defective.

Short Circuit in

Troubleshoot and repair or replace as required.

Lamp Fixture

Defective Transformer or

Troubleshoot and repair or replace as required.

Capacitor (Ballast)

LAMPS START TO LIGHT AND THEN GO OUT.

Incorrect Generator Output

Troubleshoot generator.

Incorrect Engine Speed

Check engine speed reset to 61.5 HZ no-load.

Defective Transformer or

Troubleshoot and repair or replace as required.

Capacitor (Ballast)

Defect in Ballast Wiring

Trace and repair as required.

Defect in Tower Wiring

Trace and repair as required.