A warning – Carrier 48N User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

codes, or contact your Distributor or Branch to determine
the required orifice size.

C. Adjusting Gas Input

The gas input to the unit is determined by measuring the
gas flow at the meter or by measuring the manifold pres­
sure. Measuring the gas flow at the meter is recommended

for natural gas units. The manifold pressure must be mea­
sured to determine the input of propane gas units.

1. Measuring Gas Flow at Meter Method—Natural Gas
Units

Minor adjustment can be made by changing the manifold
pressure. The manifold pressure must be maintained
between 3.2 and 3.8-in. water. If larger adjustments are

required, change main burner orifices following the recom­
mendations of national and local codes.

NOTE:

All other apphances that use the same meter must

be turned off when gas flow is measured at the meter.

Proceed as follows:

Turn off gas supply to unit.
Remove pipe plug on outlet of gas valve, then con­
nect manometer at this point. Turn on gas to unit.

Record number of seconds for gas meter test dial to
make one revolution.
Divide number of seconds in step c into 3600 (num­
ber of seconds in 1 hour).
Multiply result of step d by the number of cubic ft

shown for one revolution of test dial to obtain cubic
ft of gas flow per hour.

f. Multiply result of step e by Btu heating value of gas

to obtain total measured input in Btuh. Compare
this value with heating input shown in Table 8.
(Consult the local gas suppher if the heating value
of gas is not known.)

Example:

Assume that the size of test dial is 1 cubic ft, one

revolution takes 30 seconds, eind the heating value of the
gas is 1050 Btu/ft®, then proceed as follows:

a. 30 seconds to complete one revolution.

b. 3600 -30 = 120.

c. 120 X 1 = 120 ft® of gas flow/hr.

d. 120 X 1050 = 126,000-Btuh input.

If the desired gas input is 125,000 Btuh, only a minor
change in the manifold pressure is required.

Observe manifold pressure and proceed as follows to adjust
gas input:

Remove cover screw over regulator adjustment
screw on gas valve.
Turn regulator adjustment screw clockwise to

increase gas input, or turn regulator adjustment
screw counterclockwise to decrease input. Manifold
pressure must be between 3.2 and 3.8-in.-water.

a.

b.

c.

e.

a.

b.

A WARNING

Unsafe operation of the unit may result if manifold
pressure is outside this range. Personal injury or unit
damage may result.

c. Replace cover screw cap on gas valve.

d. Turn off gas supply to unit. Remove manometer

from pressure tap. Replace pipe plug on gas valve.
Turn on gas to unit. Check for leaks.

2. Measuring Manifold Pressure—Propane Gas Units

The main burner orifices on a propane gas unit are sized for
the unit rated input when the manifold pressure is 10.5-in.
water.

Proceed as follows to adjust gas input on a propane gas

unit:

a. Turn off gas to unit.

b. Remove pipe plug on outlet of gas valve then con­

nect memometer at this point.

c. Turn on gas to unit.

d. Remove cover screw over REG ADJ screw on gas

valve.

e. Adjust regulator adjustment screw for a manifold

pressure reading of 10.5-in.-water. Turn adjusting

screw clockwise to increase manifold pressure, or
turn adjusting screw counterclockwise to decrease

manifold pressure.

f. Replace cover screw.

g. Turn off gas to unit. Remove manometer from pres­

sure tap. Replace pipe plug on gas valve, then tmrn
on gas to unit. Check for leaks.

D. Check Burner Flame

Observe the unit heatmg operation, and watch the burner
flames through the observation port to see if they are light
blue and soft in appearance, and the flames are approxi­
mately the same for each burner. See Fig. 10.

E. Blower Heat-Relay Operation

Blower relay PCI (See the unit wiring diagram.) is located in
the control box and adjusts to permit either longer or
shorter “off” cycles. The “on” cycle is factory set for 1 min­

ute on timing. The adjusting dial on the relay (See Fig. 9) is
factory-set at the minimum position to provide optimum
performance for most installations. On unusual installa­
tions, the length of time the blower remains on may require

increasing. To increase blower operation time, rotate the
adjusting dial counter-clockwise. To decrease blower opera­
tion time, rotate dial clockwise. (Minimum time 1 minute.)

Maximum time 3 minutes.)

F. Airflow and Temperature Rise

The heating section of each size of unit is designed and
approved for heating operation within the temperature rise
range stamped on the unit rating plate.

Table 8—Rated Gas Inputs at Indicated Manifold Pressures

Model

No.

Number

of

Orifices

Gas Supply Pressure

(in. wc)

Manifold
Pressure

(In. wc)

Natural Gas

Propane Gast

Orifice

P/N

Heating

Input

(Btuh)*

Input

P/N

Heating

(Btuh)*

Natural

Propane

Min

Max

Min

Max

Natural

Propane

48NLT018, 024, 030

2

5.0

13.6

11.0

13.0

3.5

10.5

55365-44

40,000

55365-55

40,000

48NHT024, MT030, LT036, LT042

3

5.0

13.6

11.0

13.0

3.5

10.5

55365-44

60,000

55365-55

60,000

48NHT030, MT036, MT042, LT048, LT060

4

5.0

13.6

11.0

13.0

3.5

10.5

55365-44

80,000

55365-55

80,000

48NHT036, HT042, MT048, MT060

5

5.0

13.6

11.0

13.6

3.5

12.5

55365-44

100,000

55365-55

100,000

48NVT036, VT042, HT048, HT060

6

5.0

13.6

11.0

13.6

3.5

10.5

5536544

120,000

55365-55

120,000

♦Based on altitudes from sea level up to 2000 feet above sea level. For altitudes above 2000 feet, reduce input rating 4% for each 1000 feet above sea

level. In Canada, from 2000 ft. above sea level to 4,500 ft. above sea level, derate the unit 10%.

fWhen a 48N is converted to propane, the burners must be modified. See kit instructions.

11

Advertising