Carrier 48N User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

A CAUTION

Do not change the blower-motor lead connections on
460-V units from the factory setting. Damage to unit
may result.

The heating emd/or cooling airflow of 208/230-V direct-drive
blower motors can be changed by changing the lead connec­
tions of the blower motor. The motor leads are color-coded

as follows:

black = high speed
blue = medium speed

red

= low speed

NOTE:

For all 208/230 V direct-drive units, the motor lead

connected to the heat relay (L) on PCI blower control deter­
mines the heating speed and resulting air-flow; and the

motor lead connected to the cooMng relay (H) on PCI blower
control determines the coohng speed and resulting airflow.
See the unit wiring label.

To change the heating and/or coohng speed of a direct-drive
motor, connect the appropriate color-coded lead to the
appropriate relay. Connect unused motor lead to terminal
Ml on the PCI blower control.

When installing a 208- or 230-V direct-drive unit that is
factory-connected for heating and coohng speeds that are
not the same, and the same speed for both heating and cool­
ing is required for a particular application, connect the

appropriate color-coded lead to terminal H of coohng relay
and connect a field-supplied jumper between terminal L on
heat relay and terminal H of coohng relay. Connect unused

leads to terminals Ml and M2 on PCI blower control.

D. Unit Controls

All compressors have the following internal-protection
controls:

1. High-pressure Relief Valve—T\ds valve opens when the

pressure differential between the low and high side
becomes excessive.

2. Compressor Overload—This overload interrupts power

to the compressor when either the current or internal
temperature become excessive, and automatically
resets when the internal temperature drops to a safe
level. This overload may require up to 60 minutes (or

longer) to reset; therefore, if the internal overload is
suspected of being open, disconnect the electrical
power to the unit and check the circuit thru the over­
load with an ohmmeter or continuity tester.

E. Cooling Sequence of Operation

NOTE:

Although the actual unit wiring may vary slightly

from that shown in Figs. 12, 13 or 14, the sequence of opera­
tion win not be affected.

With the room thermostat SYSTEM switch in the COOL
position and the FAN switch in the AUTO position, the
cooling sequence of operation is as follows:

When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the
thermostat completes the circuit between thermostat termi­
nal “R” to terminals “Y” and “G.” These completed cir­
cuits through the thermostat connect contactor coil “C”

(through unit wire “Y”) and relay coil “IFRl” (through unit

wire “G”) across the 24-volt secondary of tremsformer

“TRAN.”

The normally open contacts of energized contactor “C”
close and complete the circuit through compressor motor
“COMP” and condenser fan motor “OFM.” Both motors
start instantly.

The set of normally open contacts of energized relay

“IFRl” closes and completes the circuit through evapora­

tor blower motor “IFM.” The blower motor starts
instantly.

NOTE:

The cooling cycle remains “on” until the room

termperature drops to point that is slightly below the cool­
ing control setting of the room thermostat. At this point,

the thermostat “breaks” the circuit between thermostat ter­
minal “R” to terminals “Y” and “G.” These open circuits

deenergize contactor coU “C” and relay coil “IFRl”. The
condenser and compressor motors stop. After a one minute
delay the blower motor stops. The unit is in a “standby”

condition, waiting for the next “call for cooling” from the
room thermostat.

Step 10—Care and Maintenance

To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic mainte­
nance must be performed on this equipment. This combina­
tion heating/cooling unit should be inspected at least once

each year by a qualified service person.

NOTE TO EQUIPMENT OWNER:

Consult your local Dealer

about the avedlability of a maintenance contract.

A WARNING

The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills,
tools, and equipment. If you do not possess these, do

not attempt to perform any maintenance on this equip­
ment other than those procedures recommended in the

Users Manual. A FAILURE TO HEED THIS WARN­
ING COULD RESULT IN SERIOUS PERSONAL

INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.

The rninimum maintenance requirements for this equipment
are as follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect cooling coil, drain pan, and condensate drain

each cooling season for cleanliness. Clean when
necessary.

3. Inspect blower motor and wheel for cleanliness and

check lubrication each heating and cooling season.
Clean and lubricate when necessary.

4. Check electrical connections for tightness and controls

for proper operation each heating and cooling season.
Service when necessary.

5. Check emd inspect heating section before each heating

season. Clean and adjust when necessary.

6. Check and clean vent screen if needed.

A WARNING

A failure to foUow these warnings could result in seri­
ous personal injury:

1. Turn off gas supply, then turn off electrical power

to the unit before performing any maintenance or
service on the unit.

2. Use extreme caution when removing panels and

parts. As with any mechanical equipment, personal
injury can result from sharp edges, etc.

3. Never place anything combustible either on, or in

contact with, the unit.

4. Should overheating occur, or the gas supply fail to

shut off, shut off the external main manual gas

valve to the unit, then shut off the electrical supply.

14

Advertising