Flare nut strainer retainer cooling, Indoor, Coil – Carrier 48N User Manual

Page 24: Flare

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

FLARE NUT STRAINER RETAINER COOLING

TO

INDOOR

COIL

FLARE

NUT

(TOWARD INDOOR COIL)

Fig. 15—Metering Device Components

Table 19—Cooling Service Analysis Chart

SYMPTOM

CAUSE

REMEDY

Compressor and
condenser fan

will not start.

Power failure

Call power company.

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker.

Defective thermostat, contactor, transformer, or

controi relay

Replace component.

Insufficient line voltage

Determine cause and correct.

Incorrect or faulty wiring

Check wiring diagram and rewire correctly.

Thermostat setting too high

Lower thermostat setting below room temperature.

Compressor will not start
but condenser fan runs.

Faulty wiring or loose connections in compressor
circuit

Check wiring and repair or replace.

Compressor motor burned out, seized, or internal
overload open

Determine cause. Replace compressor.

Defective run/start capacitor, overload, start relay

Determine cause and replace.

One leg of three-phase power dead

Replace fuse or reset circuit breaker.
Determine cause.

Compressor cycles,
(other than normally
satisfying thermostat)

Refrigerant overcharge or undercharge

Blow refrigerant, evacuate system, and recharge to

nameplate.

Defective compressor

Replace and determine cause.

Insufficient line voltage

Determine cause and correct.

Blocked condenser

Determine cause and correct.

Defective run/start capacitor, overload, or start relay

Determine cause and replace.

Defective thermostat

Replace thermostat.

Faulty condenser fan motor or capacitor

Replace.

Restriction in refrigerant system

Locate restriction and remove.

Compressor operates
continuously.

Dirty air filter

Replace filter.

Unit undersized for load

Decrease load or increase unit size.

Thermostat set too low

Reset thermostat.

Low refrigerant charge

Locate leak, repair, and recharge.

Leaking valves in compressor

Replace compressor.

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted

Clean coil or remove restriction.

Excessive head pressure

Dirty air filter

Replace filter.

Dirty condenser coil

Clean coil.

Refrigerant overcharged

Purge excess refrigerant.

Air in system

Blow refrigerant, evacuate system, and recharge.

Condenser air restricted or air short-cycling

Determine cause and correct.

Head pressure too low

Low refrigerant charge

Check for leaks, repair, and recharge.

Compressor valves leaking

Replace compressor.

Restriction in liquid tube

Remove restriction.

Excessive suction

pressure

High heat load

Check for source and eliminate.

Compressor valves leaking

Replace compressor.

Refrigerant overcharged

Purge excess refrigerant.

Suction pressure too low

Dirty air filter

Replace filter.

Low refrigerant charge

Check for leaks, repair, and recharge.

Metering device or low side restricted

Remove source of restriction.

Insufficient evaporator airflow

Increase air quantity. Check filter—replace if
necessary.

Temperature too low in conditioned area

Reset thermostat.

Outdoor ambient below 55 F

Install low-ambient kit.

Field-installed filter-drier restricted

Replace.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

^

PC 101 Catalog No. 564-816

Printed in U.S.A.

Form 48NT-9SI Pg 24

9-88

Replaces: 48NT-8SI

Tab

I

la

I

la

Advertising