Burglary protection points (audible), System test – ADT Security Services Commercial Fire & Burglary Alarm System FOCUS 200 PLUS User Manual

Page 71

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

System Test

To ensure proper operation of your FOCUS® 200 PLUS security system, it is
recommended that you periodically test all devices within your system. You
can print, display, or audibly annunciate all system tests. Before testing
protection groups and/or points, turn off the group(s) containing the points to
be tested.

Burglary Protection Points (Audible)

1. Using the operating panel’s numeric keypad, enter a valid ID code to

display Action Menu 1.

2. Bypass all protection points to be tested.

3. Press

More

to display Action Menu 2.

4. Press

Test

to display Test Menu 1.

5. Press

More

to display Test Menu 2.

6. Press

Burg pts. audibly

to audibly annunciate the test from the operating

panel and begin the system test. The display will indicate "Test in
Progress."

7. Walk through the test areas and activate each protection point to be

tested. You will hear a beep when all points are secure (normal) and a
steady tone when a point is activated.

8. When the test is complete, return to the operating panel and re-enter

your ID code to display Action Menu 1.

9. Press

Reset

to display the reset options.

10. Press

Tests

to exit the test mode and to return the system to normal

operation.

11. Press

Continue

to display Action Menu 1.

12. Unbypass those points that were bypassed for test purposes.

71

Advertising