GAS SUPPLY PIPING

Check Gas Supply
Gas pipe to your boiler must be correct size for length of

run and for total BTU per hour input of all gas utilization

equipment connected to it. Be sure your gas line complies

with local codes and gas company requirements. See Table

4 for proper pipe size.

Connecting The Gas Piping

Gas line enters boiler from right side.

• Use only piping materials and joining methods listed

as acceptable by the authority having jurisdiction, or in

the absence of such requirements, by the National Fuel

Gas Code, ANSI Z223.1/NFPA 54.

• Use pipe joint compound suitable for LP gas on male

threads only.

• Use ground joint unions.
• Install sediment trap upstream of gas controls.
• Use two pipe wrenches when making connection to gas

valve to keep it from turning.

• Install manual shut-off valve in vertical pipe about 5

feet above fl oor.

• Tighten all joints securely.
• Propane gas connections should only be made by

licensed propane installer.

• Two-stage regulation should be used by propane

installer.

• Propane gas piping should be checked out by propane

installer.

CHECKING GAS PIPING

DANGER

Fire Hazard. Do not use matches, candles, open

fl ames, or other methods providing ignition source.

Failure to comply will result in death or serious

injury.

!

Pressure test boiler and gas connection before placing

boiler in operation.

• Pressure test over 1/2 psig (3.5 kPa). Disconnect

boiler and its individual gas shutoff valve from gas

supply system.

NATURAL GAS

Pipe Capacity - BTU Per Hour Input

Includes Fittings

Length of

Pipe - FT

½”

¾”

1”

1¼”

20

92,000

190,000

350,000

625,000

40

63,000

130,000

245,000

445,000

60

50,000

105,000

195,000

365,000

PROPANE GAS

Pipe Capacity - BTU Per Hour Input

Includes Fittings

Length of

Pipe - FT

Copper Tubing *

Iron Pipe

⅝”

¾”

½”

¾”

20

131,000

216,000

189,000

393,000

40

90,000

145,000

129,000

267,000

60

72,000

121,000

103,000

217,000

* Outside diameter

Measure length of pipe or tubing from gas meter or

propane second stage regulator.

Table 4 - GAS PIPE SIZES

Figure 10 - Gas Piping

• Pressure test at 1/2 psig (3.5 kPa) or less. Isolate

boiler from gas supply system by closing manual gas

shutoff valve.

• Locate leakage using gas detector, noncorrosive

detection fl uid, or other leak detection method

acceptable to authority having jurisdiction. Do

not use matches, candles, open fl ames, or other

methods providing ignition source.

• Correct leaks immediately and retest.

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Immediately call your gas supplier from a

neighbor’s phone. Follow gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the fi re

department.

!

!