15

ELECTRICAL WIRING

Electrically bond boiler to ground in accordance with

requirements of authority having jurisdiction. Refer to Na-

tional Electrical Code, ANSI/NFPA 70.

ELECTRIC POWER SUPPLY
Run separate 120 volt circuit from separate over current

protective device in electrical service entrance panel. This

should be a 15 ampere circuit. Locate shut-off switch at

boiler. It must be turned off during any maintenance. Con-

nect 120 volt power supply to control leads L1 (HOT) and

L2.
Run a 14 gauge or heavier copper wire from boiler to

grounded connection in service panel or properly driven

and electrically grounded ground rod.

THERMOSTAT INSTALLATION

1.

Thermostat should be installed on an inside wall about

four feet above the fl oor.

2.

NEVER install a thermostat on an outside wall.

3.

Do not install a thermostat where it will be affected

by drafts, hot or cold pipes, sunlight, lighting fi xtures,

televisions, a fi replace, or a chimney.

4.

Check thermostat operation by raising and lowering

thermostat setting as required to start and stop the

burners.

5.

Instructions for the fi nal adjustment of the thermostat

are packaged with the thermostat (adjusting heating

anticipator, calibration, etc.)

Set heat anticipator at .2 amps. 24 volt thermostat con-

nects to aquastat terminals T and TV.

VENT DAMPER WIRING
Boiler is equipped with factory wired harness with 4 pin

molex plug, that plugs into 4 pin molex receptacle inside

vent damper operator.
Vent damper must be connected for boiler to operate.

If original wire as supplied with this appliance

must be replaced, replace with type 105°C

thermoplastic wire or its equivalent.

WARNING

Electrical shock hazard. Turn OFF electrical power

supply at service panel before making electrical

connections. Failure to do so could result in death

or serious injury.

!

NOTICE

Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after

servicing.