6

VENTILATION & COMBUSTION AIR

Provide combustion air and ventilation air in accordance

with the section “Air for Combustion and Ventilation,” of

the National Fuel Gas Code, ANSI Z223.1 / NFPA 54, or

applicable provisions of local building codes.
Provide make-up air where exhaust fans, clothes dryers,

and kitchen ventilation equipment interfere with proper

operation.
National Fuel Gas Code recognizes several methods

of obtaining adequate ventilation and combustion air.

Requirements of the authority having jurisdiction may

override these methods.

• Engineered Installations. Must be approved by

authority having jurisdiction.

• Mechanical Air Supply. Provide minimum of 0.35

cfm per Mbh for all appliances located within space.

Additional requirements where exhaust fans installed.

Interlock each appliance to mechanical air supply

system to prevent main burner operation when

mechanical air supply system not operating.

• All Indoor Air. Calculate minimum volume for all

appliances in space. Use a different method if

minimum volume not available.

A. Standard Method. Cannot be used if known air

infi ltration rate is 0.40 air changes per hour. See

Table 3 for space with boiler only. Use equation for

multiple appliances.
Volume ≥ 50 ft

3

x Total Input [Mbh]

B. Known Air Infi ltration Rate. See Table 3 for

space with boiler only. Use equation for multiple

appliances. Do not use an air infi ltration rate

(ACH) greater than 0.60.
Volume ≥

21 ft

3

⁄ACH x Total Input [Mbh]

C. Refer to National Fuel Gas Code for opening

requirements between connected indoor spaces.

• All Outdoor Air. Provide permanent opening(s)

communicating directly or by ducts with outdoors.

A. Two Permanent Opening Method. Provide opening

commencing within 12 inches of top and second

opening commencing within 12 inches of bottom of

enclosure.

 Direct communication with outdoors or

communicating through vertical ducts. Provide

minimum free area of 1 in² per 4 Mbh of total

input rating of all appliances in enclosure.

 Communicating through horizontal ducts.

Provide minimum free area of 1 in² per 2

Mbh of total input rating of all appliances in

enclosure.

B. One Permanent Opening Method. Provide opening

commencing within 12 inches of top of enclosure.

Provide minimum clearance of 1 inch on sides/back

and 6 inches on front of boiler (does not supersede

clearance to combustible materials).

• Refer to National Fuel Gas Code for additional require-

ments for louvers, grilles, screens and air ducts.

• Combination Indoor and Outdoor Air. Refer to National

Fuel Gas Code for application information.

National Gas and Propane Installation Code Requires

providing air supply in accordance with:

• Section 8.2 and 8.3 when combination of appliances

has a total input of up to and including 400 Mbh (120

kW).

• Section 8.4 when combination of appliances has total

input exceeding 400 Mbh (120 kW).

• Refer to Natural Gas and Propane Installation Code

for specifi c air supply requirements for enclosure

or structure where boiler is installed, including air

supply openings and ducts.

Table 3 - Minimum Room Volume, Indoor Air Only*

Input Mbh

Standard

Method

Known Air Infi ltration Rate Method ACH (Air Changes Per Hour)

0.1

0.2

0.3

0.4

0.5

0.6

75

3750

15750

7875

5250

3938

3150

2625

112.5

5625

23625

11813

7875

5906

4725

3938

150

7500

31500

15750

10500

7875

6300

5250

187.5

9375

39375

19688

13090

9844

7875

6563

255

11250

47250

23625

15750

11813

9450

7875

262.5

13125

55125

27563

18375

13781

11025

9188

299

14950

62790

31395

20930

15698

12558

10465

* Table values based on boiler only. Add volume for any additional appliances.