BLOCKED VENT SAFETY SWITCH
(BLOCKED VENT SAFETY SHUTOFF)
Blocked vent safety switch is manual reset disc thermostat

with fi xed setpoint (340°F), and normally closed contacts. It

is located at relief opening of integral draft diverter. In event

of chimney or venting system blockage causing products of

combustion to spill out of relief opening, blocked vent safety

switch disc heats up and blocked vent safety switch contacts

open, shutting down fl ow of gas to main burners by removing

power to gas valve.
In event blocked vent safety switch contacts open, reset

button on back of switch will pop up. Blocked vent safety

switch must be reset manually, after switch has cooled off,

by pushing reset button down. Check venting system and

chimney for blockage when restoring system to operating

condition. DO NOT operate boiler without blocked vent

safety switch.

ROLLOUT SWITCH
(FLAME ROLLOUT SAFETY SHUTOFF)
Rollout switch is temperature-sensitive fuse link device.

Located on boiler base just outside fi re box. In event of

heat exchanger fl ueway blockage causing fl ame to roll

out of fi re box, fuse does not change in appearance when

blown.
If rollout switch blows, it must be replaced with exact

replacement. Check heat exchanger fl ueways for blockage

when restoring system to operating condition. DO NOT

operate system without rollout switch.