Antifreeze added to boilers must be nontoxic, and

must be of type specifically intended for use in closed

hydronic heating systems. Under no circumstances

should automotive antifreeze be used. Antifreeze used

in any boiler may reduce capacity by 10% or more and

increase fuel consumption. Tankless coil performance

will fall as concentration of antifreeze is increased. Refer

to boiler and piping water volumes tables.

BOILER WATER VOLUMES

Number of

Boiler Section

Total Volume

(Gallons)

3

9.6

4

11.6

5

13.7

PIPING WATER VOLUMES

PIPE SIZE

COPPER PIPE

FACTOR

STEEL PIPE

FACTOR

½”

82.5

63.5

¾”

40.0

36.0

1”

23.3

22.2

1 ¼”

15.3

12.8

1 ½”

10.8

9.5

2”

6.2

5.8

Divide total length of piping in feet by appropriate factor

in table to determine volume in gallons.

SYSTEM PIPING ARRANGEMENT