Dunkirk EW Empire II Series II User Manual

Page 20

Advertising
background image

20

Air Supply For Combustion:

• Do not install boiler in rooms with insufficient air, unless

corrective steps are taken.

• It may be necessary to install windows or cut holes in

a door to rooms used for supply air to obtain sufficient

combustion air and prevent less than atmospheric air

pressure in that room.

• If there is a lack of combustion air, burner flame will be

dark orange and formation of soot will occur in heating

unit.

• In buildings of conventional frame, brick, or stone

construction that do not have utility rooms, basement

windows, or stair doors, air infiltration is normally

adequate to provide enough air for combustion and for

operation of barometric draft control.

• Room used for supplying combustion air should be

isolated from any area served by exhaust fans.

• Refer back to the section on Fresh Air For Combustion

for additional sizing guidelines.

Draft Regulators:

Barometric draft regulator is required

for controlling draft through boiler. Mount barometric draft

regulator in chimney connector. Refer back to section on

“Chimney And Chimney Connections”. Once draft regulator

is installed, use draft gauge to adjust to proper opening:

A. Combustion chamber over fire draft will be

approximately 0.01” WC to 0.02” WC.

B. Stack draft will be approximately 0.02” WC. to

0.04” WC.

C. Larger installation, greater draft will be required in

stack to obtain desired over fire draft.

Start:

Fill entire system with water. Vent all air from

system following section for Filling The Boiler.

Fuel Units And Oil Lines:

• Install oil line(s) to oil burner.
• Recommend using heavy wall copper tubing and

flared fittings, not compression fittings.

• All connections and joints must be absolutely airtight.

Use an appropriate non-hardening thread sealing

compound on the threaded connections, not Teflon

tape.

• See fuel unit data sheet furnished with the burner for

sizing, lift, and length of tubing recommendations.

Oil burner is equipped with single stage fuel unit

with bypass plug removed for single pipe installation.

Satisfactory where fuel supply is on same level as or

above burner permitting gravity flow of oil. Per NFPA 31

requirements, never exceed 3 psig pressure to inlet side of

fuel unit.

When necessary to lift oil to burner, two pipe installation

is required. Run return line between fuel unit and oil

supply. When two pipe installation is used, bypass plug

(furnished with burner) must be installed in fuel unit. Refer

to fuel unit instructions furnished with burner for specific

instructions on installing bypass plug. Do not exceed fuel

unit manufacturer’s recommendations for running vacuum.

NOTICE

If lift exceeds 14 feet for Beckett or Carlin burners

or 11 feet for Riello burners, two stage fuel unit is

required with return line.

Install oil filter of adequate size inside building between

tank shutoff valve and oil burner. For ease of servicing,

locate shutoff valve and filter near oil burner.

OPERATING THE BOILER

Advertising