Adjust Operating Controls

: Use the following settings

for first adjustment:

High Limit:

Baseboard and Convectors 200°F

Standing Radiators 180°F

Low Limit

(when used) 140º ( increase if hotter domestic

water is required, low limit set point must be at least 20°F less

than high limit set point)

When low limit is used, set ELL parameter on L7248

Honeywell control to ON. Boilers factory equipped with

tankless coils, are already set to ON.

Adjust Thermostat Heat Anticipator To: 0.2

Amp

s

CHECKING AND ADJUSTING CONTROLS

NOTICE

You or your installer must follow these instructions

carefully.

WARNING

Burn, scald hazard. Do not attempt to start the

burner when excess oil has accumulated, when

the unit is full of vapor, or when the combustion

chamber is very hot.

!

Check Thermostat Operation:

Follow instructions included with your thermostat.

Locate thermostat five feet above the floor on inside wall.

Locate thermostat to sense average room temperature,

avoid the following:

THERMOSTAT LOCATIONS TO AVOID

DEAD

SPOTS

HOT SPOTS

COLD SPOTS

Behind

doors

Concealed pipes Concealed pipes

or ducts

Fireplace

TV sets

Stairwells drafts

Corners &

alcoves

Radios

Doors drafts

Lamps

Unheated room

on other side of

wall

Direct sunlight

Kitchens

When temperature on thermostat is set above indicated

thermostat temperature, boiler’s burner should start. Verify

that when room temperature reaches selected temperature

setting, thermostat should turn boiler’s burner off, and once

room temperature falls few degrees boiler starts operating

again.

Do not start burner unless all cleanout doors are

secured in place.