Dunkirk EW Empire II Series II User Manual

Page 24

Advertising
background image

24

Annually

: Recommend flue passages, combustion

chamber area (target wall, fire door insulation,

durablanket), burner adjustment, control operation, and

boiler seals (fire door gasket or silicone seal, cast iron

sectional seals, flue collector) be checked once each year

by trained Service Technician.

Before The Start Of Each Heating Season

(or when

system has been shut down for extended periods of time)

recheck whole system for water, oil, and vent piping leaks.

Replace or patch any leaks or faulty seals.

Vent Pipe:

Visually inspect entire venting system once a

month for any signs of leakage, deterioration, or soot build

up. If vent pipe shows any signs of leaking or deterioration,

replace it immediately. If it shows any signs of soot

build up, clean vent pipe and have burner settings and

combustion checked by trained Service Technician.

Safety Relief Valve:

Valve should open automatically

when system pressure exceeds pressure rating (usually 30

psi) of safety relief valve. Should valve ever fail to open

under this condition, shut down the system. Drain system

until system pressure is reduced below safety relief valve

pressure rating. Contact Service Technician to replace the

valve and inspect heating system to determine cause, may

indicate equipment malfunction. Safety relief valve should

be tested monthly during heating season. Prior to testing,

make certain discharge pipe is properly connected to valve

outlet and arranged so as to contain and safely dispose of

boiler discharge. Hold trip lever fully open for at least five

seconds in order to flush free any sediment that may lodge

on valve seat. Permit valve to snap shut. Refer to valve

manufacturer’s instructions packaged for more details.

Conventional Expansion Tank

: Tank may become

water logged or may receive excess air. Frequent automatic

opening of safety relief valve indicates water logging. High

boiler temperature accompanied by unusually low radiation

unit temperature (and “knocking” noises) indicates excess

air in the tank. To correct either condition, close valve

between boiler and tank. Drain tank until empty. Check all

tank plugs and fittings, tighten as necessary. Open valve

between boiler and tank. Water will rise to normal height in

tank if system has automatic fill valve, otherwise manually

refill system.

Diaphragm Expansion Tank

: Tank may become

water logged. Frequent automatic opening of safety relief

valve indicates water logging. High boiler temperature

accompanied by unusually low radiation unit temperature

(and “knocking” noises) indicates excess air in the tank. To

correct this condition, replace diaphragm expansion tank.

Water System:

If system is to remain out of service

during freezing weather, drain it completely (water left in

system may freeze and will crack pipes and/or boiler).

Tankless Coil (Or Cover Plate) Gasket:

Gasket

should be checked at least twice year for leakage, replace if

necessary. If gasket is replaced, make sure that when coil

plate (or cover plate) is reattached, ten nuts are torqued

in alternating pattern to insure equal force is applied to

entire gasket creating good seal. Nuts should be torqued so

gasket does not squeeze out from behind the plate.

Oil Burner:

Oil burner maintenance is listed in this

manual under “Operating The Boiler”.

Never burn garbage or paper in the unit, never leave

combustible material around it.

MAINTENANCE

Advertising