Dunkirk EW Empire II Series II User Manual

Page 19

Advertising
background image

19

How A Hot Water System Operates

Entire heating system (boiler, piping, and radiation units)

is filled with water. As water in the boiler is heated, it

is circulated from top of boiler through supply main to

radiation units. Cooler water in radiation units flows back

through return piping through return main into the boiler.

This arrangement provides positive and rapid response to

the thermostat.

Filling The System With Water

OPTION #1 This method utilizes boiler piping as shown in

figure on page 6.

A. Close main shutoff valve, isolation valves, and zone

valves (if applicable). If bypass piping is installed,

also close two throttling valves. Leave boiler service

shutoff valve (if installed) and balancing valves to

each heating zone fully open.

B. Open following valves in order: drain valve for power

purging, isolating valves before and after boiler

circulator (if applicable), both throttling valves (if

applicable), and then open fill line shutoff valve. Water

will fill bypass piping and push air through piping and

out power purging drain valve. When power purging

drain valve runs air free, close bypass piping throttling

valve (leaving throttling valve to supply piping fully

open).

C. Next, open isolation valve (or zone valve) to first

zone. Water will fill piping and push any air out power

purging drain valve. When power purging drain valve

runs air free, close isolation valve or zone valve).

Repeat this procedure for remaining heating zones.

D. Once all zones are filled with water and purged of air,

close power purging drain valve and fill line shut off

valve, open main shutoff valve, and adjust throttling

valves and balancing valves as required.

OPTION #2

• Close air vents on all radiation units.
• Open valves to radiation units. Verify boiler drain valve,

expansion tank drain cock, and air bleed screw on

expansion tank drain fitting are closed.

• Open fill valve on piping to expansion tank.
• Open water inlet to boiler and leave it open.
• Open air vent on lowest radiation unit.
• When all air has escaped and water starts to flow from

vent, close it.

• Go to next radiation unit, and repeat this process until

finishing with highest radiation unit.

• If heating system has automatic vents, this manual

venting is unnecessary but it will speed up proper filling

of the system.

If system is a closed expansion tank system, automatic fill

valve is needed. Leave automatic fill valve open to refill

system automatically as needed.

Note initial fill pressure on boiler’s temperature / pressure

gauge, which should be 10-15 psig. Any lowering of

pressure from its initial fill pressure indicates loss of water

due to leakage. Automatic fill valve should then compensate

for this water pressure loss. If it does not, manually open

this valve to refill system until needle is again pointing to

same pressure reading. Instructions are packaged with

valve.

FILLING THE BOILER

Advertising