Spectrum Controls 1762sc-IF8U User Manual

Page 26

Advertising
background image

3-6

MicroLogix™ 1200 IO Universal Input Module



User's Manual Pub. 0300243‐02 Rev. B 

To Select

Make these bit settings

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

604

NiFe

518

1 1

1

0

0

150

ohm

1 1

1

0

1

1000

ohm

1 1

1

1

0

3000

ohm

1 1

1

1

1

Data

Format

6

Engineering

Units X1

0

0

Engineering

Units X10

0

1

Raw/

Proportional Data

1

0

Scaled

for

PID

1 1

CJC Temp

Type

7

(Only when

bit 3 is set)

Raw CJC Temp

x

8

0

Adjusted CJC Temp

x

8

1

2/3/4 Wire

RTD

(Only valid for

RTD/R ranges)

2

Wire

0 0

3

Wire

w/

Comp

0 1

3

Wire

w/o

Comp

1 0

4

Wire

1 1

Temperature

Scale

(Only valid for

temperature ranges)

Deg C

0

Deg F

1


Table 3-3 lists the number of counts for each of the supported data ranges.

Note: The engineering unit data formats represent real engineering
temperature units provided by the module to the controller. The
raw/proportional counts, scaled-for-PID and percent of full-scale data
formats may yield the highest effective resolutions, but may also require
that you convert channel data to real engineering units in your control
program.

Table 3-3 (Data Ranges)

Input Type

Range

Eng. Units

Eng Units X10 Raw/Prop

PID

B Type Thermocouple

300 to 1820 ˚C
(572 to 3308 ˚F)

3000 to 18200
(5720 to 32767)

9

300 to 1820
(572 to 3308)

-32768 to 32767

0 to 16383

C Type Thermocouple

0 to 2315 ˚C
(32 to 4199 ˚F)

0 to 23150
(320 to 32767)

9

0 to 2315
(32 to 4199)

-32768 to 32767

0 to 16383

E Type Thermocouple

-270 to 1000 ˚C
(-454 to 1832 ˚F)

-2700 to 10000
(-4540 to 18320)

-270 to 1000
(-454 to 1832)

-32768 to 32767

0 to 16383

J Type Thermocouple

-210 to 1200 ˚C
(-346 to 2192 ˚F)

-2100 to 12000
(-3460 to 21920)

-210 to 1200
(-346 to 2192)

-32768 to 32767

0 to 16383

K Type Thermocouple

-270 to 1370 ˚C

-2700 to 13700

-270 to 1370

-32768 to 32767

0 to 16383




6

Refer Table 3-3 for data ranges.

7

Raw CJC Temp = All 8 channels will display the current CJC sensor temperature.

Adjusted CJC Temp = Each channel will display it’s adjusted CJC temperature.

8

X = don’t care

9

When configured for Fahrenheit, the maximum temperature that can be displayed by the Engineering X1

data format is 32767 or 3276.7 ˚F. If you need to read temperatures above 3276.7 ˚F, use the
Engineering X10 data format.