1-2

MicroLogix™ 1200 IO Universal Input Module



User's Manual Pub. 0300243‐02 Rev. B 

Input Type

Range

N Type Thermocouple -210 to 1300 ˚C

(-346 to 2372 ˚F)

R Type Thermocouple 0 to 1768 ˚C

(32 to 3214 ˚F)

S Type Thermocouple 0 to 1768 ˚C

(32 to 3214 ˚F)

T Type Thermocouple -270 to 400 ˚C

(-270 to 752 ˚F)

100 Ω Pt α 0.385

-200 to 850 ˚C

(-328 to 1562 ˚F)

200 Ω Pt α 0.385

-200 to 850 ˚C

(-328 to 1562 ˚F)

500 Ω Pt α 0.385

-200 to 850 ˚C

(-328 to 1562 ˚F)

1000 Ω Pt α 0.385

-200 to 850 ˚C

(-328 to 1562 ˚F)

100 Ω Pt α 0.3916

-200 to 630 ˚C

(-328 to 1166 ˚F)

200 Ω Pt α 0.3916

-200 to 630 ˚C

(-328 to 1166 ˚F)

500 Ω Pt α 0.3916

-200 to 630 ˚C

(-328 to 1166 ˚F)

1000 Ω Pt α 0.3916

-200 to 630 ˚C

(-328 to 1166 ˚F)

10 Ω Cu α 0.426

-100 to 260 ˚C

(-148 to 500 ˚F)

100 Ω Ni α 0.618

-100 to 260 ˚C

(-148 to 500 ˚F)

120 Ω Ni α 0.672

-80 to 260 ˚C

(-112 to 500 ˚F)

604 Ω NiFe α 0.518

-100 to 200 ˚C

(-148 to 392 ˚F)

Resistance

0 to 150 Ω
0 to 1000 Ω
0 to 3000 Ω

Voltage

+/- 50 mV
+/- 100 mV
0 to 5V
1 to 5V
+/- 10V
0 to 10V

Current

4 to 20 mA
0 to 20 mA

Section 1.3
Data Formats

For each module the data can be configured for:

 Engineering units x 1
 Engineering units x 10
 Scaled-for-PID
 Raw/proportional data

Section 1.4
Filter
Frequencies

The module uses a digital filter that provides high frequency noise rejection for each
input signal. The filter for each channel is programmable allowing you to select from four
different filter frequencies:

 4 Hz
 17 Hz
 62 Hz
 470 Hz