Chapter 1 module overview – Spectrum Controls 1762sc-IF8U User Manual

Page 7

Advertising
background image

User's Manual Pub. 0300243‐02 Rev. B 

Chapter 1
Module Overview

This chapter describes the 1762sc-IF8u Universal input module and explains how the
module reads current, voltage, RTD, resistance and thermocouple/millivolt analog input
data. Included is information about:

 General description
 Input types and ranges
 Data Formats and filter frequencies
 Hardware Features
 System overview and module operation

Section 1.1
General
Description

The universal input module supports current, voltage, RTD, resistance, thermocouple and
millivolt type inputs. The module digitally converts and stores analog data from any
combination mentioned above. Each input channel is individually configured via
software for a specific input device, data format, filter frequency, and provides open-
circuit, over-range, under-range detection and indication.

!

Attention

The IF8u module supports up to 8 channels of voltage, current or
thermocouple or up to 4 channels of RTD/resistance. Each
RTD/resistance input requires two channels. Refer to the table below
for possible combinations.

Table 1-1 (Channel Configurations)
8 channels Voltage/Current/Thermocouple + 0 channels RTD/Resistance
6 channels Voltage/Current/Thermocouple + 1 channels RTD/Resistance
4 channels Voltage/Current/Thermocouple + 2 channels RTD/Resistance
2 channels Voltage/Current/Thermocouple + 3 channels RTD/Resistance
0 channels Voltage/Current/Thermocouple + 4 channels RTD/Resistance

Section 1.2
Input Types
and Ranges

The tables below list the input types and their associated ranges.

Table 1-2 (Input Types)
Input Type

Range

B Type Thermocouple 300 to 1820 ˚C

(572 to 3308 ˚F)

C Type Thermocouple 0 to 2315 ˚C

(32 to 4199 ˚F)

E Type Thermocouple -270 to 1000 ˚C

(-454 to 1832 ˚F)

J Type Thermocouple -210 to 1200 ˚C

(-346 to 2192 ˚F)

K Type Thermocouple -270 to 1370 ˚C

(-454 to 2498 ˚F)

Advertising