Spectrum Controls 1762sc-IF8U User Manual

Page 28

Advertising
background image

3-8

MicroLogix™ 1200 IO Universal Input Module



User's Manual Pub. 0300243‐02 Rev. B 

Section 3.5
Read Input
Data

Input data is read for each channel, converted to a scaled digital value, and stored in the
input file. Use the addressing scheme below to locate the 8 input words used for
channels 0 through 7, respectively.

(1)

I

/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins

with slot 1.

The layout for the input file is shown below.

Table 3-4 (Input Data)

Word Description

I:e.0 Analog Data Channel 0
I:e.1 Analog Data Channel 1 ( 0 if Ch 0 RTD/Resistance)
I:e.2 Analog Data Channel 2
I:e.3 Analog Data Channel 3 ( 0 if Ch 2 RTD/Resistance)
I:e.4 Analog Data Channel 4
I:e.5 Analog Data Channel 5 ( 0 if Ch 4 RTD/Resistance)
I:e.6 Analog Data Channel 6
I:e.7 Analog Data Channel 7 ( 0 if Ch 6 RTD/Resistance)

!

Attention

Status data is not available for the 1762sc-IF8u module.

Section 3.6
Module
Update Time

The module update time is determined by the number of channels enabled and by the
filter frequency selected for each channel.

ADC Filter

Frequency

Filter Frequency

(-3dB point)

Conversion Time

Module update

470 Hz

109 Hz

20 ms

= sum of conversion

times for each

enabled channels

62 Hz

14 Hz

45 ms

17 Hz

4 Hz

135 ms

4Hz

1 Hz

495 ms