MicroLogix™ Combo Analog Input/Output Module

10 

Publication 0100161-01 Rev. B


Terminal Block Layout


Grounding the cable shield at the module end only usually
provides sufficient noise immunity. However, for best cable

shield performance, earth ground the shield at both ends, using a
0.01µF capacitor at one end to block AC power ground currents,

if necessary.

Labeling the Terminals

A write-on label is provided with the module. Remove the label from the door,

mark the identification of each terminal with permanent ink, and slide the label
back into the door.

TC/Voltage

Input Path

MicroLogix™ Combo Analog Input/Output Module

15 

Publication 0100161-01 Rev. B

 

To Select

Make these bit settings

7

6

5

4

3

2

1

0

Input Type

4 to 20 mA

0

0

0 to 20 mA

0

1

Reserved

1

0

Channel Disabled

1

1

Open Circuit

(For Module)

1

Upscale

0

Zero

1

Temperature

Scale

(For Module)

1

Deg C

0

Deg F

1

                                                            

1

 This is a module wide setting which is only recognized within the 

configuration for Channel 4. The corresponding bit in Channel 5 is ignored. 