Wiring the finger-safe terminal block – Spectrum Controls 1762sc-IF4OF4 User Manual

Page 11

Advertising
background image

MicroLogix™ Combo Analog Input/Output Module

14 

Publication 0100161-01 Rev. B

This table describes the channel specific configuration registers that are individually

selectable for output channels 0 through 3.

To Select

Make these bit settings

7

6

5

4

3

2

1

0

Output Type

4 to 20 mA

0

0

0

0 to 20 mA

0

0

1

-10 to 10 V

0

1

0

0 to 10 V

0

1

1

1 to 5 V

1

0

0

0 to 5 V

1

0

1

Reserved

1

1

0

Channel Disabled

1

1

1

Data Format

Scaled for PID

0

0

Engineering Units

0

1

Percent Range

1

0

Raw/Proportional Data

1

1

Unused

0 0 0

 

This section details the channel specific configuration registers that are individually
selectable for channels 4 and 5

To Select

Make these bit settings

7

6

5

4

3

2

1

0

Filter

Frequency

(Ignored if

Display CJC)

17 Hz

0

0

4 Hz

0

1

62 Hz

1

0

470 Hz

1

1

Data Format

Engineering Units X1

0

0

Engineering Units X10

0

1

Raw/Proportional
Data

1

0

Scaled for PID

1

1

MicroLogix™ Combo Analog Input/Output Module

11 

Publication 0100161-01 Rev. B

Wiring the Finger-Safe Terminal Block


Be careful when stripping wires. Wire fragments that fall into
a module could cause damage when power is applied. Once
wiring is complete, ensure the module is free of all metal
fragments.

When wiring the terminal block, keep the finger-safe cover in place.

1. Route the wire under the terminal pressure plate. You can use the stripped

end of the wire or a spade lug. The terminals will accept a 6.35 mm (0.25

in.) spade lug.

2. Tighten the terminal screw making sure the pressure plate secures the

wire. Recommended torque when tightening terminal screws is 0.904 Nm

(8 in-lbs).

3. After wiring is complete, remove the debris shield.

If you need to remove the finger-safe cover, insert a screw

driver into one of the square wiring holes and gently pry the
cover off. If you wire the terminal block with the finger-safe

cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way

Advertising