Specification Description
Accuracy - Voltage
Outputs

System accuracy at 25° C: ± 20 mV maximum
System accuracy at -20-60°C: ± 50 mV maximum

Accuracy - Current
Outputs

System accuracy at 25° C: ± 50 uA maximum
System accuracy at -20-60°C: ± 75 uA maximum

Output Resolution

Voltage Output

370µV per bit average when using RAW format in ±10V range and 0-
10V range
185µV per bit average when using RAW format in 0-5 or 1-5V ranges

Current Output

380nA per bit when using RAW format for all current ranges

Differential Nonlinearity 1 LSB (see resolution for LSB size)
Output Ripple

<15mV ripple for voltage or current

Output Impedance

Current: >1Megohm, Voltage: <1 ohm (MRD)

Output Load

Current: 0 ohm min, 500 ohm max,
Voltage: >=1k ohm at 10V output (10 mA), includes wire resistance.

Maximum Output
Inductive and
Capacitive Load

0.1mH
1µF

Output Settling Time

<1ms to 63% of full scale

Output Channel glitch

Current mode = < ± 1V for 20ms at maximum load
Voltage mode = < ± 0.4V for 20ms and < ±- 1V for 1.5ms with 1k
ohm load

Output Protection

±24V @25˚ C for 1 minute on any channel, with any range and value

Output Short Ckt
Protection

Yes, continuous. (IEC 1131-2 requirement) with any range and value

MicroLogix™ Combo Analog Input/Output Module

Publication 0100161-01 Rev. B


Remove Power

Remove power before removing or installing this module.

When you remove or install a module with power applied, an
electrical arc may occur. An electrical arc can cause personal

injury or property damage by:

 sending an erroneous signal to your system’s field

devices, causing unintended machine motion

 causing an explosion in a hazardous environment

 causing permanent damage to the module’s

circuitry


Electrical arcing causes excessive wear to contacts on both

the module and its mating connector. Worn contacts may
create electrical resistance.

Mounting

The 1762sc-IF4OF4 is to be used with the MicroLogix™ 1100, 1200 or 1400
processor.

Do not remove protective debris strip until after the
module and all other equipment near the module is

mounted and wiring is complete. Once wiring is complete
and the module is free of debris, carefully remove protective

debris strip. Failure to remove strip before operating can
cause overheating.

Advertising