Power requirements, Input specifications, Panel mounting – Spectrum Controls 1762sc-IF4OF4 User Manual

Page 7

Advertising
background image

MicroLogix™ Combo Analog Input/Output Module

18 

Publication 0100161-01 Rev. B

Specification Description
Hazardous Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T4a

Radiated and
Conducted Emissions

IEC61000-6-4 FCC Part 15B Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity
(IEC61000-4-2)

4 kV contact, 8 kV air

Radiated Immunity
(IEC61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation, 900 MHz
& 1890 MHz 100% amplitude modulation

Fast Transient Burst
(IEC61000-4-4)

4 kV

Surge Immunity
(IEC61000-4-5)

2 kV Line - Line, 4 kV Line - Gnd

Conducted Immunity
(IEC61000-4-6)

10V, 0.15 to 80 MHz

Input Specifications

Specification Description
Calibrated Accuracy

For all specified input accuracy ranges, the accuracy for the fastest
two filters will be the specified accuracy plus the repeatability for the
particular filter chosen.

Thermocouple Inputs

Linearization per ITS-90
System accuracy at 25°C (4 and 17 Hz filters):
Type J (-180°C to 1200°C): ±1.0 degrees C maximum
Type K (-200°C to 1370°C): ±2.0 degrees C maximum
Type E (-200°C to 1000°C): ±1.0 degrees C maximum
Type T (-190°C to 400°C): ±2.0 degrees C maximum

System accuracy at -20-60 C (4 and 17 Hz filters):
Type J (-180°C to 1200°C): ±5.0 degrees C maximum
Type K (-200°C to 1370°C): ±6.0 degrees C maximum
Type E (-200°C to 1000°C): ±4.5 degrees C maximum
Type T (-190°C to 400°C): ±4.0 degrees C maximum

The above limits do not include the cold junction compensation or
thermocouple sensor errors.

CJC Profile accuracy

± 4.0 degrees C maximum Temperature correlation to target terminal

CJC accuracy (sensor
and measurement)

± 1.0 degrees C maximum Reading/Conversion of the sensor -20 to
80C input values

CJC Resolution

± 0.5 degrees C maximum for -20-80C input values

Voltage Inputs

System accuracy at 25° C (4 and 17 Hz filters):
± 3 mV maximum for 0-5V inputs
± 3 mV maximum for 1-5V inputs
± 10 mV maximum for 0-10V inputs
± 10 mV maximum for ±10V inputs

System accuracy at -20-60° C (4 and 17 Hz filters):
± 6 mV maximum for 0-5V inputs
± 6 mV maximum for 1-5V inputs
± 20 mV maximum for 0-10V inputs
± 20 mV maximum for ±10V inputs

MicroLogix™ Combo Analog Input/Output Module

Publication 0100161-01 Rev. B


For environments with extreme vibration and shock

concerns, use the panel mounting method described
below, instead of DIN rail mounting.

Panel Mounting

Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6

panhead screws may also be used, but a washer may be needed to ensure a good
mechanical contact. Mounting screws are required on every module.

Power Requirements

The maximum number of IF4OF4 modules that can be installed in a system
depends on the maximum bus current draw of the module and the maximum bus
current provided by the PLC. The IF4OF4 module has the following power
requirements.

5 VDC

24 VDC

30 mA

3.0 W Max (125mA max at 24V)

Use the table below to determine the maximum number of IF4OF4 modules that
can be installed in a MicroLogix system.