Wiring, Grounding the module, System wiring guidelines – Spectrum Controls 1762sc-IF4OF4 User Manual

Page 9

Advertising
background image

MicroLogix™ Combo Analog Input/Output Module

16 

Publication 0100161-01 Rev. B

This table describes the channel specific configuration registers that are individually

selectable for channels 6 and 7.

To Select

Make these bit settings

7

6

5

4

3

2

1

0

Filter Frequency

(Ignored if Display CJC)

17 Hz

0

0

4 Hz

0

1

62 Hz

1

0

470 Hz

1

1

Data Format

Engineering Units X1

0

0

Engineering Units X10

0

1

Raw/Proportional Data

1

0

Scaled for PID

1

1

Input Type

4 to 20 mA

0 0

0

0

0 to 20 mA

0 0

0

1

-10 to 10 V

0 0

1

0

0 to 10 V

0 0

1

1

1 to 5 V

0 1

0

0

0 to 5 V

0 1

0

1

Type J TC

0 1

1

0

Type K TC

0 1

1

1

Type E TC

1 0

0

0

Type T TC

1 0

0

1

Display CJC channel temp 1 0

1

0

Reserved

1 0

1

1

Reserved

1 1

0

0

Reserved

1 1

0

1

Reserved

1 1

1

0

Channel Disabled

1 1

1

1

MicroLogix™ Combo Analog Input/Output Module

Publication 0100161-01 Rev. B

Wiring

Grounding the Module

Grounding for this product is provided by the MicroLogix™ 1100, 1200 or 1400
CPU via the bus ribbon cable. Refer to Industrial Automation Wiring and Grounding

Guidelines, Allen-Bradley publication 1770-4.1, for additional information.

System Wiring Guidelines

Consider the following when wiring your system:

 The analog common (COM) is not connected to earth ground inside the

module. All terminals are electrically isolated from the system.

 Output channel returns are common

 Input channel to channel isolation is limited to ±13 VDC from the output

return voltage.

 Use Belden™ 8761, or equivalent, shielded wire.

 Under normal conditions, the drain wire (shield) should be connected to

the metal mounting panel (earth ground) as close to the module as

possible. Keep the shield connection to earth ground as short as possible.

 To ensure optimum accuracy for voltage type inputs, limit overall cable

impedance by keeping all analog cables as short as possible. Locate the

I/O system as close to your voltage type sensors or actuators as possible.

 The 1762sc-IF4OF4 module does not provide loop power for analog

inputs. Use a power supply that matches the input transmitter

specifications.

 Digital and analog power must be supplied by an Isolated Secondary

Limited Energy Low Voltage source.

 Use supply wires for 20˚ C above surrounding ambient.