Installation

1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use
in clean, dry environments (Pollution degree 2

(1)

) and to circuits not exceeding

Over Voltage Category II

(2)

(IEC 60664-1).

(3)

Prevent Electrostatic Discharge


Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow

these guidelines when you handle the module:

 Touch a grounded object to discharge static

potential.

 Wear an approved wrist-strap grounding device.

 Do not touch the bus connector or connector pins.

 Do not touch circuit components inside the

module.

 If available, use a static-safe work station.
 When not in use, keep the module in its static-

shield box.






(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except
that occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level
transient voltages are controlled and do not exceed the impulse voltage capability of the product’s
insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission
(IEC) designations.

MicroLogix™ Combo Analog Input/Output Module

21 

Publication 0100161-01 Rev. B

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-

hazardous locations only. The following WARNING statement applies to use in
hazardous locations.

EXPLOSION HAZARD

 Substitution of components may impair

suitability for Class I, Division 2.

 Do not replace components or disconnect

equipment or change the current switch

selection switch position unless power has been
switched off.

 Do not disconnect equipment unless power has

been removed or the area is known to be non-
hazardous.

 This product must be installed in an enclosure.
 In Class I, Division 2 applications, the bus

connector must be fully seated and the bus
connector cover must be snapped in place.

 In Class I, Division 2 applications, all modules

must be mounted in direct contact with each

other as shown on page 6. If DIN rail mounting
is used, an end stop must be installed ahead of

the controller and after the last 1762 I/O
module.

 All wiring must comply with N.E.C. article 501-

4(b).