Spectrum Controls 1762sc-OF8 User Manual

Page 16

Advertising
background image

2-6

MicroLogix™ 1200 IO 8 Ch Output Module



User’s Manual Pub. 0300246-01 Rev. B

Figure 2-4

Note: Use the pull loop on the connector to disconnect modules. Do not
pull on the ribbon cable.

!

Attention

EXPLOSION HAZARD

In Class I, Division 2 applications, the bus connector must be

fully seated and the bus connector cover must be snapped in
place.

In Class I, Division 2 applications, all modules must be

mounted in direct contact with each other as shown on page 2-
4. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.

Section 2.6
Field Wiring
Connections

Consider the following when wiring your system:

General

 Power and output wiring must be in accordance with Class 1, Division 2 wiring

methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.

 The analog common (COM) is not connected to earth ground inside the module.

All terminals are electrically isolated from the system.

 To ensure optimum accuracy for voltage type outputs, limit overall cable

impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.

 Digital and analog power must be supplied by an Isolated Secondary Limited

Energy Low Voltage source.

 Use Belden™ 8761, or equivalent, shielded wire.