Spectrum Controls 1762sc-OF8 User Manual

Page 36

Advertising
background image

A-2

MicroLogix™ 1200 IO 8 Ch Output Module



User’s Manual Pub. 0300246-01 Rev. B

Specification

Value

Product Code

21

Agency
Certification

C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous
Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B,
C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T6

Radiated and
Conducted
Emissions

EN55011

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity
(IEC61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity
(IEC61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed
carrier

Fast Transient
Burst
(IEC61000-4-4)

2 kV, 5 kHz

Surge Immunity
(IEC61000-4-5)

1 kV galvanic gun

Conducted
Immunity
(IEC61000-4-6)

10V, 0.15 to 80 MHz

8




8

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 2700

MHz.