Chapter 2: Installation and Wiring

2-7

User’s Manual Pub. 0300246-01 Rev. B

!

Attention

USE SUPPLY WIRES SUITALE FOR 20°C ABOVE SURROUNDING
AMBIENT

!

Attention

UTILISER DES FILS D’ALIMENTATION QUI CONVIENNENT A
UNE TEMPERATURE DE 20°C AU-DESSUS DE LA
TEMPERATURE AMBIANTE

Grounding

 This product is intended to be mounted to a well-grounded mounting surface

such as a metal panel. Additional grounding connections from the module’s
mounting tabs or DIN rail (if used) are not required unless the mounting surface
cannot be grounded.

 Under normal conditions, the drain wire (shield) should be connected to the

metal mounting panel (earth ground). Keep shield connection to earth ground as
short as possible.

 Ground the shield drain wire at one end only. The typical location is as at the

module end.

 If it is necessary to connect the shield drain wire at the module end, connect it to

earth ground using a panel or DIN rail mounting screw.

 Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-

Bradley publication 1770-4.1, for additional information.

Noise Prevention

 Route field wiring away from any other wiring and as far as possible from

sources of electrical noise, such as motors, transformers, contactors, and ac
devices. As a general rule, allow at least 15.2 cm (6 in.) of separation for every
120V of power.

 Routing field wiring in a grounded conduit can reduce electrical noise.
 If field wiring must cross ac or power cables, ensure that they cross at right

angles.

 If noise persists for a device, try grounding the opposite end of the cable shield

or ground both ends of the shield.

2.6.1 Wiring Diagram

Refer to the following wiring diagrams for field wiring connections.

Figure 2-5 (Wiring Diagram)