MicroLogix™ 1200 IO 8 Ch Output Module



User’s Manual Pub. 0300246-01 Rev. B

Table 3-3 (Data Words 1 through 4)

To Select

Channels 1, 3, 5, or 7

Channels 0, 2,4 or 6

15

14

13

12

11

10

9

8

7 6 5 4 3

2

1

0

Output

Type

4 to 20 mA

0 0

0

0

0

0

0 to 20 mA

0

0

1

0

0

1

-10 to 10 V

0

1

0

0

1

0

0 to 10 V

0

1

1

0

1

1

1 to 5 V

1

0

0

1

0

0

0 to 5 V

1

0

1

1

0

1

Reserved

1

1

0

1

1

0

Channel Disabled

1

1

1

1

1

1

Data

Format

Scaled for PID

0 0

0 0

Engineering Units

0 1 0 1

Percent Range

1 0 1 0

Raw/Proportional
Data

1 1 1 1

Unused

0 0 0 0 0 0