VERSATEC BASE 50Hz SERIES INSTALLATION MANUAL

General

Be sure the available power is the same voltage and phase

as that shown on the unit serial plate. Line and low voltage

wiring must be done in accordance with local codes or the

National Electric Code, whichever is applicable.

Power Connection

Connect the incoming line voltage wires to L1 and L2 of the

contactor for single-phase unit. Consult the Electrical Data

tables for correct fuse sizes.

Aurora Base Control Box

Electrical Connections

220 Volt Operation

All Versatec Base Series 220-240 units are factory wired for

240 volt operation. For 220 volt operation, the red and blue

transformer wires must be switched on terminal strip PS.

CAUTION: When installing a unit with a

variable speed ECM blower motor in 420/50/3

voltage, a neutral wire is required to allow

proper unit operation.

For Aurora Base Control, set SW2-1, FP1, on the printed

circuit board for applications using a closed loop antifreeze

solution to 15°F [-9.4°C]. On applications using an open

loop/ground water system (or closed loop no antifreeze), set

this dip switch to 30°F [-1.1°C], the factory default setting.

(Refer to the Dip Switch Field Selection table).