Controls - upc ddc control (optional) cont, Versatec base 50hz series installation manual – WaterFurnace Versatec Base User Manual

Page 40

Advertising
background image

40

VERSATEC BASE 50Hz SERIES INSTALLATION MANUAL

RNet Sensor Physical and Electrical Data

Sensing Element

Range

Accuracy

Temperature (on non-Humidity models)

(-20° C to 50° C)

(0.2° C)

Temperature (on Humidity models)

(10° C to 40° C)

(0.3° C)

Humidity

10% to 90%

±1.8% typical

CO2

400 to 1250 PPM

1250 to 2000 PPM

±30PPM or +/-3% of reading (greater of two)

±5% of reading plus 30 PPM

VOC

0 to 2,000 PPM

±100 PPM

Power Requirements

Sensor Type

Power Required

Temperature Only

All Models

12 Vdc @ 8 mA

Temperature with Humidity

All Models

12 Vdc @ 15 mA (idle) to 190 mA

(CO2 measurement cycle)

Temp with VOC, or Temp/VOC/Humidity

All Models

12 Vdc @ 60 mA

Temp with CO2 , or Temp/ CO2/Humidity

All Models

12 Vdc @ 15 mA (idle) to 190 mA

(CO2 measurement cycle)

Power Supply

A controller supplies the Rnet sensor network with 12 Vdc @ 210 mA. Additional

power may be required for your application. See sensor ZS Installation Guide

Communication

115 kbps Rnet connection between sensor(s) and controller

15 sensors max per Rnet network; 5 sensors max per control program

Local Access Port

For connecting a laptop computer to the local equipment for maintenance and commissioning

Environmental Operating Range

(0° - 50° C), 10% to 90% relative humidity, non-condensing

Mounting Dimensions

Standard 4”x 2” electrical box using provided 6/32” x 1/2” mounting screws

Controls - UPC DDC Control (optional) cont.

Advertising