Electrical data cont – WaterFurnace Versatec Base User Manual

Page 18

Advertising
background image

18

VERSATEC BASE 50Hz SERIES INSTALLATION MANUAL

Electrical Data cont.

Variable Speed ECM Motor

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Blower

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/HACR

Breaker

MCC

RLA

LRA

005

220-240/50/1

198/264

13.1

5.5

24.0

4.0

9.5

10.9

15

006

220-240/50/1

198/264

12.6

6.7

46.0

4.0

10.7

12.4

15

380-420/50/3

342/462

6.0

2.9

30.0

4.1

7.0

7.7

10/15

007

220-240/50/1

198/264

14.0

8.0

46.0

4.0

12.0

14.0

20

380-420/50/3

342/462

6.4

3.2

30.0

4.1

7.3

8.1

10/15

009

220-240/50/1

198/264

17.7

9.9

67.0

4.0

13.9

16.4

25

380-420/50/3

342/462

7.1

3.8

34.0

4.1

7.9

8.9

10/15

010

380-420/50/3

342/462

7.7

4.2

34.0

4.1

8.3

9.4

10/15

012

220-240/50/1

198/264

25.5

13.8

81.0

4.0

17.8

21.3

30

380-420/50/3

342/462

8.0

5.6

44.0

4.1

9.7

11.1

15

015

380-420/50/3

342/462

12.0

6.7

55.0

6.9

13.6

15.3

20

017

380-420/50/3

342/462

11.5

7.1

55.0

6.9

14.0

15.8

20

HACR circuit breaker in USA only 12/5/14

Caution: When installing a unit with a Variable Speed ECM blower motor in 380-420/50/3 voltage, a neutral wire is
required to allow proper unit operation
.

Advertising