Operating Parameters

Operating Limits

Single Speed Models

SI

Entering

Water

Temp

°C

Water

Flow

L/s/kW

Cooling -- No Hot Water Generation

Suction

Pressure

kPa

Discharge

Pressure

kPa

Superheat Subcooling

Water

Temp

Rise

°C

Air Temp

Drop

°C DB

-1.1

0.09

793 - 862

1034 - 1172

11 - 19

6 - 9

9 - 12

9 - 13

0.19

724 - 827

896 - 1000

11 - 19

6 - 9

4 - 6

9 - 13

10

0.09

896 - 965

1482 - 1620

7 - 11

4 - 8

9 - 12

9 - 13

0.19

883 - 951

1310 - 1448

7 - 11

4 - 8

4 - 7

9 - 13

21.1

0.09

951 - 1020

1931 - 2137

6 - 9

6 - 9

8 - 12

9 - 13

0.19

938 - 1007

1724- 1931

6 - 9

4 - 8

4 - 7

9 - 13

32.2

0.09

1000 - 1069 2413 - 2620

5- 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055 2206 - 2413

5- 8

4 - 8

3 - 6

9 - 13

43.3

0.09

1000 - 1063 2896 - 3102

5- 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055 2792 - 2999

5- 8

4 - 8

3 - 6

9 - 13

Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.

Heating performance based on entering air temperature of 70º F DB.

Heating - No Hot Water Generation

Suction Pres-

sure kPa

Discharge

Pressure

kPa

Superheat

Subcooling

Water

Temp

Drop

°C

Air Temp

Rise

°C DB

503-586

1862- 2103

4 - 8

2 - 6

3 - 6

8 - 12

531 - 621

1931 - 2172

4 - 8

2 - 6

2 - 4

9 - 13

669 - 758

1999 - 2241

6 - 9

2 - 6

5 - 7

12 - 16

703 - 793

2068- 2310

6 - 9

2 - 6

4 - 6

13 - 17

896- 1000

2206 - 2448

7 - 11

2 - 6

6 - 8

17 - 20

931 - 1034

2241 - 2482

7 - 11

2 - 6

4 - 7

18 - 21

1034 - 1103

2413 - 2689

7 - 11

2 - 6

6 - 8

17 - 20

1069- 1038

2517 - 2792

7 - 11

2 - 6

4 - 7

18-21

12/5/14

Operating Limits

Cooling

Heating

(°C)

(°C)

Air Limits

Min. Ambient Air

7.2

7.2

Rated Ambient Air

26.7

21.1

Max. Ambient Air

37.8

29.4

Min. Entering Air

10.0

4.4

Rated Entering Air db/wb

27/19

20.0

Max. Entering Air db/wb

43/28.3

26.7

Water Limits

Min. Entering Water

-1.1

-6.7

Normal Entering Water

10-43.3

-1.1

Max. Entering Water

48.9

32.2

NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependent upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.