Electrical data – WaterFurnace Versatec Base User Manual

Page 17

Advertising
background image

17

VERSATEC BASE SERIES 50Hz INSTALLATION MANUAL

Electrical Data

5-Speed ECM Motor

Model

Rated

Voltage

Voltage Min/

Max

Compressor

Blower

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/HACR

Breaker

MCC

RLA

LRA

005

220-240/50/1

198/264

13.1

5.5

24.0

4.1

9.6

11.0

15

006

220-240/50/1

198/264

12.6

6.7

46.0

4.1

10.8

12.5

15

380-420/50/3

342/462

6.0

2.9

30.0

2.1

5.0

5.7

10/15

007

220-240/50/1

198/264

14.0

8.0

46.0

4.1

12.1

14.1

20

380-420/50/3

342/462

6.4

3.2

30.0

2.1

5.3

6.1

10/15

009

220-240/50/1

198/264

17.7

9.9

67.0

4.1

14.0

16.5

25

380-420/50/3

342/462

7.1

3.8

34.0

2.1

5.9

6.9

10/15

010

380-420/50/3

342/462

7.7

4.2

34.0

2.1

6.3

7.4

10/15

012

220-240/50/1

198/264

25.5

13.8

81.0

7.6

21.4

24.9

35

380-420/50/3

342/462

8.0

5.6

44.0

4.0

9.6

11.0

15

015

380-420/50/3

342/462

12.0

6.7

55.0

4.0

10.7

12.4

15

017

380-420/50/3

342/462

11.5

7.1

55.0

4.0

11.1

12.9

15

HACR circuit breaker in USA only 12/5/14

Advertising