Installation

Operating Manual PMI 5
1002241­EN­05

22

5.5

Installing the unit

When installing the unit, please note the following:

}

For stability reasons, the front panel, console or control cabinet should have a wall
thickness of at least 2.5 mm.

}

To avoid a build­up of heat, a distance of a 10 cm/3.94" should be kept free all round
the system.

}

Ensure the information given for the ambient and operating temperatures in the tech­
nical details is observed.

}

IP65 protection can only be guaranteed when

the fixing screws are sufficiently tightened (min. 0.2 Nm).

the gasket is not damaged.

the wall thickness is at least 2.5 mm.

}

Protect the system against falling down, i.e. ensure that the fixing screws are firmly
tightened.

5.6

PMI 509 Installation

Fig.: PMI 509 Installation

NOTICE

The torque setting for the fixing screws may not exceed 0.3 Nm.